Chapter 12
279
Device states of the MELSEC-WS safety controller
12
Device states of the MELSEC-WS safety controller
The MELSEC-WS safety controller knows different device states during operation.
Some device states require a user intervention, e.g. the state transition from Stop to
Run or vice versa using the Setting and Monitoring Tool. Other states are based on
the internal self-test of the safety controller, e.g. Internal error. The following table
summarizes the device states of the safety controller.
MS LED
Meaning
Notes
Supply voltage is outside
range
Switch on the supply voltage and check it
at the terminals A1 and A2.
Red/Green (1
Hz)
A self test is being carried
out or the system is being
initialized
Please wait …
Green (1 Hz)
System is in Stop state
Start the application in the Setting and
Monitoring Tool.
Green (2 Hz)
Identify (e.g. for Flexi Link)
–
Green
System is in Run state
–
Red (1 Hz)
Invalid configuration
Check the module type and version of the
CPU module and safety I/O modules
whose MS LED flashes
Red/Green.
If appropriate, adapt the configuration
using the Setting and Monitoring Tool.
For detailed diagnostics information refer
to the Setting and Monitoring Tool.
Red (2 Hz)
Critical error in the system,
possibly in this module.
Application is stopped. All
outputs are switched off.
Switch the supply voltage off and on
again. If the error is not eliminated after
multiple repetition, replace this module.
For detailed diagnostics information refer
to the Setting and Monitoring Tool.
Red
Critical error in the system,
possibly in another
module. Application is
stopped. All outputs are
switched off.
Switch the supply voltage off and on
again.
If the error is not eliminated after multiple
repetition, replace the module which
displays
Red (2 Hz). If this is not the
case, use the diagnostic functions of the
Setting and Monitoring Tool to narrow
down the respective module.
CV LED
Meaning
Notes
Configuration in progress
Please wait …
Yellow (2 Hz)
Storing of configuration
data in the memory plug
(non-volatile memory)
Supply voltage may not be interrupted
until the storage process has been
completed.
Yellow (1 Hz)
Unverified configuration
Verify configuration with the Setting and
Monitoring Tool.
Yellow
Verified configuration
–
Symbol description:
: LED off,
: LED lights up, : LED flashes
Table
115
:
Device status and LED
displays on the CPU module
Summary of Contents for SW1DNN-WS0ADR-B
Page 2: ......
Page 288: ...Chapter 15 285 Annex ...
Page 289: ...Chapter 15 286 Annex ...
Page 290: ...Chapter 15 287 Annex ...
Page 291: ...Chapter 15 288 Annex ...
Page 292: ...Chapter 15 289 Annex ...
Page 293: ...Chapter 15 290 Annex ...
Page 294: ...Chapter 15 291 Annex ...
Page 295: ...Chapter 15 292 Annex ...
Page 296: ...Chapter 15 293 Annex ...
Page 297: ...Chapter 15 294 Annex ...
Page 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Page 299: ...Chapter 15 296 Annex ...
Page 300: ...Chapter 15 297 Annex ...
Page 301: ...Chapter 15 298 Annex ...
Page 302: ...Chapter 15 299 Annex ...
Page 303: ...Chapter 15 300 Annex ...
Page 304: ...Chapter 15 301 Annex ...
Page 305: ...Chapter 15 302 Annex ...
Page 306: ...Chapter 15 303 Annex ...
Page 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Page 308: ...Chapter 15 305 Annex ...
Page 309: ...Chapter 15 306 Annex ...
Page 310: ...Chapter 15 307 Annex ...
Page 311: ...Chapter 15 308 Annex ...
Page 312: ...Chapter 15 309 Annex ...
Page 313: ...Chapter 15 310 Annex ...
Page 314: ...Chapter 15 311 Annex ...
Page 321: ......