Chapter 12
280
Device states of the MELSEC-WS safety controller
12.1 Changing the device state
Specific state changes in the MELSEC-WS safety controller are carried out manually
in the Setting and Monitoring Tool. These changes in the device state are:
change from Stop to Run
change from Run to Stop
In order to change the device state, click on the
Stop application
or
Run application
button next to the representation of the modules in the hardware configuration.
Icon
Function
Description
Run
Sets the system into the Run state.
Stop
Sets the system into the Stop state.
If the configuration is verified, the MELSEC-WS safety controller will go into the Run
state automatically after the voltage supply has been switched on. If the configuration
is not verified, the system must be set into the Run state manually using the Setting
and Monitoring Tool.
12.2 Behaviour on startup
When the MELSEC-WS safety controller changes from the Stop state to the Run
state:
The
First logic cycle
status bit of the CPU module is High for the logic execution
time. This status bit is available as a CPU input element in the logic editor.
All timers and states including the error states of the function blocks are reset.
12.3 Software reset of the CPU module
It is possible to reset the CPU module via software (i.e. without interrupting the voltage
supply), if the Setting and Monitoring Tool is connected with the CPU module.
How to perform a software reset:
In the
Hardware configuration
view, right click on the CPU module in the
Configuration area
and select the
Software reset
command from the context
menu.
If you are not logged in as Administrator, you will be prompted to log in now.
A safety message will appear. Click on
Yes
to reset the CPU module.
Before you reset the CPU module, check whether the system is in a safe state!
If you reset the CPU module, the outputs (e.g. the
Enable
output) could change their
status. The
Software reset
command should only be used when the hazardous area
has been checked visually and nobody is in the hazardous area or has access to the
hazardous area while the CPU module is being reset.
If the configuration is verified, the CPU module will change back into the Run state
automatically after the reset. If the configuration is not verified, you will have to start
the CPU module manually using the Setting and Monitoring Tool.
Table
116
:
Run button and Stop button
Note
ATTENTION
Note
Summary of Contents for SW1DNN-WS0ADR-B
Page 2: ......
Page 288: ...Chapter 15 285 Annex ...
Page 289: ...Chapter 15 286 Annex ...
Page 290: ...Chapter 15 287 Annex ...
Page 291: ...Chapter 15 288 Annex ...
Page 292: ...Chapter 15 289 Annex ...
Page 293: ...Chapter 15 290 Annex ...
Page 294: ...Chapter 15 291 Annex ...
Page 295: ...Chapter 15 292 Annex ...
Page 296: ...Chapter 15 293 Annex ...
Page 297: ...Chapter 15 294 Annex ...
Page 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Page 299: ...Chapter 15 296 Annex ...
Page 300: ...Chapter 15 297 Annex ...
Page 301: ...Chapter 15 298 Annex ...
Page 302: ...Chapter 15 299 Annex ...
Page 303: ...Chapter 15 300 Annex ...
Page 304: ...Chapter 15 301 Annex ...
Page 305: ...Chapter 15 302 Annex ...
Page 306: ...Chapter 15 303 Annex ...
Page 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Page 308: ...Chapter 15 305 Annex ...
Page 309: ...Chapter 15 306 Annex ...
Page 310: ...Chapter 15 307 Annex ...
Page 311: ...Chapter 15 308 Annex ...
Page 312: ...Chapter 15 309 Annex ...
Page 313: ...Chapter 15 310 Annex ...
Page 314: ...Chapter 15 311 Annex ...
Page 321: ......