Chapter 9
227
Logic programming – Function blocks
Parameters of the function block
Parameter
Possible values
Dynamic cam input
With
Without
Min. reset pulse time
100
ms
350
ms
Reset input
With
Without
Disable monitoring input
With
Without
Use fault present
With
Without
Enable output
The
Enable
output is used to stop the press and is connected to another
complementary press function block, e.g. Press setup or Press single stroke. If no
error was detected, the
Enable
output is High.
If any error in the contact signal sequence is detected, the
Enable
output changes to
Low, the corresponding error output changes to High and the
Reset required
output
changes to High. A valid reset sequence at the
Reset
input is then required.
The
Enable
output also changes to Low if Monitoring gets disabled.
Reset input
A valid reset sequence at the
Reset
input is a Low-High-Low transition with a
minimum pulse duration of 100 ms or 350 ms and maximum 30 s. Shorter and longer
pulses are ignored.
Ensure that the transitions of the signals for resetting fulfill the requirements of
the safety standards and regulations!
In case of a short-circuit to High (to 24 V DC) at a physical input, the evaluated signal
can have a pulse when the signal is reset due to the short-circuit detection. If such a
pulse can result in a dangerous state in the machine, the following points have to be
observed:
Ensure protected cable laying for the signal line (due to cross-circuiting to other
signal lines).
No short-circuit detection, i.e. do not reference to test outputs.
Safety-relevant signals have to conform to standards and regulations to be
applied!
Always take the valid national, regional and local regulations and standards into
consideration for your application. Type C standards such as EN 692 and EN 693
contain requirements how safety-relevant signals have to be used. For example, the
restart signal may have to be protected by suitable means in case of overrun errors
(e.g. by a key switch or in a closed control cabinet).
If the
Reset
input is disabled, an error can be reset only by stopping the logic
execution, e.g. by a power cycle or by changing the system state from the Run state to
the Stop state and back to the Run state with the Setting and Monitoring Tool.
Table 107:
Parameters of the Eccentric
press contact function block
ATTENTION
Summary of Contents for SW1DNN-WS0ADR-B
Page 2: ......
Page 288: ...Chapter 15 285 Annex ...
Page 289: ...Chapter 15 286 Annex ...
Page 290: ...Chapter 15 287 Annex ...
Page 291: ...Chapter 15 288 Annex ...
Page 292: ...Chapter 15 289 Annex ...
Page 293: ...Chapter 15 290 Annex ...
Page 294: ...Chapter 15 291 Annex ...
Page 295: ...Chapter 15 292 Annex ...
Page 296: ...Chapter 15 293 Annex ...
Page 297: ...Chapter 15 294 Annex ...
Page 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Page 299: ...Chapter 15 296 Annex ...
Page 300: ...Chapter 15 297 Annex ...
Page 301: ...Chapter 15 298 Annex ...
Page 302: ...Chapter 15 299 Annex ...
Page 303: ...Chapter 15 300 Annex ...
Page 304: ...Chapter 15 301 Annex ...
Page 305: ...Chapter 15 302 Annex ...
Page 306: ...Chapter 15 303 Annex ...
Page 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Page 308: ...Chapter 15 305 Annex ...
Page 309: ...Chapter 15 306 Annex ...
Page 310: ...Chapter 15 307 Annex ...
Page 311: ...Chapter 15 308 Annex ...
Page 312: ...Chapter 15 309 Annex ...
Page 313: ...Chapter 15 310 Annex ...
Page 314: ...Chapter 15 311 Annex ...
Page 321: ......