Chapter 9
159
Logic programming – Function blocks
9.8.4
Adjustable off-delay timer
Function block diagram
General description
The Adjustable off-delay timer function block delays the switching-off of the
Enable
output by an adjustable duration. Four individual delay times can be configured, each
of which can be activated via a related
Delay
input. The overall delay is the sum of all
activated delay times.
Parameters of the function block
Parameter
Possible values
Off delay time 1
0 = disabled.
0 to 600 seconds in steps of 10 ms.
If the value is not 0, the related input is activated. In this case, the value
has to be greater than the logic execution time.
The overall delay (sum of all delay times) is limited to 600 seconds.
Off delay time 2
Off delay time 3
Off delay time 4
The timer begins with the delay sequence when a falling edge (High to Low) occurs at
the
Control
input. If the timer has expired after the selected overall delay period, the
Enable
output changes also to Low, provided the
Control
input remains Low. If the
Control
input changes to High, the
Enable
output is set to High immediately and the
delay timer is reset.
If during a running delay sequence any
Delay
input changes its value, the
Time
changed
output changes to High and remains High until the
Control
input becomes
High again.
The effective overall delay time depends on the
Delay
inputs that were High at the
moment when the falling edge at the
Control
input has occurred. This means that a
change on the
Delay
inputs during a delay sequence has no effect on the current
delay sequence.
If the
Control
input is Low in the first logic cycle after transition from the Stop state to
the Run state, the
Enable
output remains Low as well.
Sequence/timing diagram
Figure 138:
Function block diagram for
the Adjustable off-delay
timer function block
Table 66:
Parameters of the
Adjustable off-delay timer
function block
Figure 139:
Sequence/timing diagram
for the Adjustable off-delay
timer function block with Off
delay time 1 and Off delay
time 2
Summary of Contents for SW1DNN-WS0ADR-B
Page 2: ......
Page 288: ...Chapter 15 285 Annex ...
Page 289: ...Chapter 15 286 Annex ...
Page 290: ...Chapter 15 287 Annex ...
Page 291: ...Chapter 15 288 Annex ...
Page 292: ...Chapter 15 289 Annex ...
Page 293: ...Chapter 15 290 Annex ...
Page 294: ...Chapter 15 291 Annex ...
Page 295: ...Chapter 15 292 Annex ...
Page 296: ...Chapter 15 293 Annex ...
Page 297: ...Chapter 15 294 Annex ...
Page 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Page 299: ...Chapter 15 296 Annex ...
Page 300: ...Chapter 15 297 Annex ...
Page 301: ...Chapter 15 298 Annex ...
Page 302: ...Chapter 15 299 Annex ...
Page 303: ...Chapter 15 300 Annex ...
Page 304: ...Chapter 15 301 Annex ...
Page 305: ...Chapter 15 302 Annex ...
Page 306: ...Chapter 15 303 Annex ...
Page 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Page 308: ...Chapter 15 305 Annex ...
Page 309: ...Chapter 15 306 Annex ...
Page 310: ...Chapter 15 307 Annex ...
Page 311: ...Chapter 15 308 Annex ...
Page 312: ...Chapter 15 309 Annex ...
Page 313: ...Chapter 15 310 Annex ...
Page 314: ...Chapter 15 311 Annex ...
Page 321: ......