N. Par. Description
Default
U.M.
Min.
Max.
27.22
Offset start point (Cooling)
0.0
°C
-30.0
P 27.23
27.23
Offset end point (Cooling)
10.0
°C
P 27.22
50.0
27.24
Maximum setpoint offset (Cooling)
0.0
°C
-30.0
50.0
27.25
Offset start point (Heating)
0.0
°C
-30.0
P 27.26
27.26
Offset end point (Heating)
10.0
°C
P 27.25
50.0
27.27
Maximum setpoint offset (Heating)
0.0
°C
-30.0
50.0
30.01
Supervision presence configuration
0
-
0
1
30.02
BMS address configuration
11
-
1
207
30.03
BMS protocol configuration [0: Standard | 1: Modbus | 2: GSM Modem | 3: LON | 4: Bacnet | 5: TCP/IP | 6:
WinLoad]
1
-
0
6
30.04
BMS baud rate configuration [0: 1200 | 1: 2400 | 2: 4800 | 3: 9600 | 4: 19200 | 5: 38400]
4
-
0
5
30.05
ON/OFF configuration from BMS [0: Disabled | 1: Enabled]
0
-
0
1
30.06
Summer/Winter switch configuration from BMS [0: Disabled | 1: Enabled]
0
-
0
1
30.09
Enable for adjustment according to the temperature supplied from BMS [0: Disabled | 1: Enabled]
0
-
0
1
30.11
Enable the stop of direct Freecooling from supervisor [0: Disabled | 1: Enabled]
0
-
0
1
31.01
Alarm A contact status configuration [0: NO | 1: NC]
0
-
0
1
31.02
Alarm B contact status configuration [0: NO | 1: NC]
0
-
0
1
31.03
Fire/smoke alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.04
Phase Sequence alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.10
Air flow alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.11
Ambient air temperature probe alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.12
Ambient humidity probe alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.13
Differential pressure probe alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.14
Delivery air temperature probe alarm address on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.16
External air temperature probe alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.18
Electric heater alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.19
T+H probe offline alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.23
Inverter IO expansion offline alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.24
Network transducer offline alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.25
Humidifier CPY offline module alarm addressing [0: A | 1: None | 2: B]
0
-
0
2
31.42
Humidifier life expired alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.43
Humidifier discharge alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.44
Humidifier insufficient water alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.45
Humidifier low current alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.46
Humidifier high current alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.47
Humidifier generic alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.49
Flooding alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.50
LAN alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.51
Low temperature alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.52
High temperature alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.53
Low humidity alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
31.54
High humidity alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2