TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
26
Mask of the terminal
Description
N. Par.
Compressor
Access mask to Compressors submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
--------------- P12.01
MIN time ON comp.:
180s
--------------- P12.02
MIN time OFF comp.:
180s
Parameters for setting
Minimum compressor ON time
Minimum compressor OFF time
12.01
12.02
--------------- P12.03
MIN time ON-ON:
same compressor: 360s
Parameters for setting
Minimum time between two ON's of the same compressor
12.03
Valve
Access mask to valves submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
--------------- P13.05
EEV status:
N
Parameters for setting the electronic valve (N:disabled - Y:enabled)
13.05
Safety
Mask confirming access to the Protections submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to
return to the submenu.
--------------- P14.03
Probe
alarm delay time: 060s
--------------- P14.04
Low Pressure
alarm delay time: 180s
Parameters for setting
Sensors alarm delay
Low pressure alarm delay
14.03
14.04
--------------- P14.08
Cooling set point
lower limit: 10.0°C
Parameters for setting the Manufacturer lower limit cooling setpoint
14.08
--------------- P14.14
Max t. for man. test:
1800s
Parameters for setting
Maximum manual operation time
Maximum manual electronic valve operation time
14.14
14.15