TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
68
2.8.2
Table of internal humidifier alarms with CPY control
The internal humidifier alarms managed by the CPY control are transmitted by the CPY control to the EV controller via the serial line.
The CPY control alarm codes are grouped below for each alarm that is read by the controller.
Differently from alarms, warnings forwarded by the CPY to the EV controller are not grouped into notifications, but can only be displayed in the internal humidifier
dedicated mask.
CPY warnings
Code
Description
0
No warning
1
CY: Maintenance warning
2
EA: Foam present
3
CP: Cylinder depletion forewarning
4
CL: Depleted cylinder
5
E2: Damaged Eeprom
Refer to the CPY manual for further info.
EV
CPY alarms
Code
Display description
Type
Code
Red indicator LED
Description
195
Humidifier Board
Offline
Al-Auto
1
2 slow flashes
Device Offline
402
Life timer expired
Reset/Clean cylinder
Al-Auto
3
8 fast flashes
Mn - Cylinder life
404
Humidifier:
Drain alarm
Al-Auto
12
5 slow flashes
Ed - Drain alarm
406
Humidifier:
Loss of Water
Al-Auto
11
3 slow flashes
EF - Missing water
408
Humidifier:
Low Current
Al-Auto
8
4 slow flashes
EP - Low production
410
Humidifier:
High Current
Al-Auto
4
5 fast flashes
EC - High conductivity
7
2 fast flashes
EH - High current
412
Generic alarm
Humidifier
Al-Auto
2
I64/I82 val. Incorrect
5
4 fast flashes
E1 - Params not dwnld
6
3 fast flashes
E0 - Calib.Par. not ok
9
8 slow flashes
EU - Full cylinder
10
7 slow flashes
E3 - Probe not conn.
540
Room Humidity
Below Min. Limit
S-Auto
541
Room Humidity
Above Max. Limit
S-Auto