TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
51
Mask of the terminal
Description
N. Par.
Info
Access mask to Info menu.
Press "Up" or "Down" to scroll through the other masks and "Esc" to return to the menu selection list.
Submenu that can be used to change user password and display software info.
Insert a NEW
USER
password
0000
Sets a new “User” password.
Warning
: the value set in this field is the one and only to access the “User” menu.
Ev
Code ME 28.00 EN
HW pCO5+S
NAND 50MB
Flash 2MB + 7MB + 4MB
Ram 2048KB
Boot 05.01 Bios06.21
This mask contains the reference information of the software [Code ME 28.00 EN].
The closed padlock symbol shows that the board is provided with its propriety software.
The second part of the mask shows information about the hardware: size (S), memories (NAND, Flash, Ram) and
the versions of the installed operating system (boot and bios).
Historical
Access mask to Alarms Log menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
Filter
for alarm event:
Location: ALL
Mask selecting the alarm type from the display history. It is possible to select from COMPRESSOR, CIRCUIT,
UNIT, and SYSTEM alarms. For a description of the location field, please refer to the “EVENTS” chapter
15:32:28 11/05/12
pLAN Address: 01
Event n° 004
SET A002 Type:AUTO
Wrong Power Phases
Sequence
Location :PLANT
Action :UNIT
Mask displaying the event history. Each event recorded contains the following details:
•
Date and time
•
Unit pLAN address (if there is a LAN controller network)
•
Event number
•
Engagement or disengagement event (SET, RESET)
•
Event code
•
Type of reset (AUTO, MANUAL)
•
Event description
•
Event localisation (COMPR, CIRCUIT, UNIT, PLANT)
•
Type of event block action (COMPR, CIRC, UNIT, CW, HU, EH, FN)
In/Out
Access mask to In/Out menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.
DIGITAL INPUT STATUS:
ID1 ID8
ID2
ID3
ID4
ID5
ID6
ID7
Displays the status of the digital inputs. The number of displayed inputs depends on the unit type.
For the meaning of each digital input, please refer to the “input/output configuration tables”