TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
31
Mask of the terminal
Description
N. Par.
--------------- P21.17
%RH band to deact.
freec. damper: 01.0%RH
Parameter for setting the humidity band to disable the Freecooling damper
21.17
--------------- P21.18
Freecooling damper
management during
compr. alarm status:
N
Parameter for configuring Freecooling damper management with compressor alarm (N:disabled - Y:enabled)
21.18
--------------- P21.19
Set point for freec.
damper during compr.
alarm: 01.0°C
Parameter for setting the Setpoint (T_
ROOM
-T_
EXTERNAL
) to regulate the Freecooling damper with compressor alarm
21.19
--------------- P21.20
Band for freec. damper
during compr. alarm:
00.5°C
Parameter for setting the Freecooling damper regulation band with compressor alarm
21.20
Settings
Access mask to Settings submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu. The Settings menu contains the parameters relative to the alarm settings.
--------------- P22.92
Unit gas type:
R32
Parameter used to set the type of gas used in the cold circuit
22.92
--------------- P22.01
Low temperature alarm
set point: 10°C
--------------- P22.02
High temperature alarm
set point: 32°C
Parameter for setting the Low temperature alarm setpoint
Parameter for setting the High temperature alarm setpoint
22.01
22.02
--------------- P22.03
Low humidity alarm
set point: 30%RH
--------------- P22.04
High humidity alarm
set point: 80%RH
Parameter for setting the Low humidity alarm setpoint
Parameter for setting the High humidity alarm setpoint
22.03
22.04
--------------- P22.13
Set unit working hours
to maintenance: 00000h
--------------- P22.14
Set comp. 1 working h.
to maintenance: 00000h
Parameter for setting the unit operating hours setpoint for maintenance
Parameter for setting the compressor 1 operating hours setpoint for maintenance
22.13
22.14