Mask of the terminal
Description
N. Par.
--------------- P50.07
Set point dehumdif. by
LAN limits: 75%RH
--------------- P50.08
Set point humdif. by
LAN limits: 35%RH
Parameters for setting
Dehumidification setpoint for LAN limits
Humidification setpoint for LAN limits
50.07
50.08
--------------- P50.09
MIN room temperature
for deumid OFF: 23.0°C
Parameter for setting the minimum room temperature for dehumidifier off
50.09
Unit
Access mask to unit menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.
INTERNAL FAN
Speed: 100%
Regulation Type:
STANDARD
Mask that displays the speed of the internal fans and type of adjustment
24.0 °C 15.0 °C
35.0 °
Active probe value display mask
•
Return temperature probe
•
Delivery temperature probe
•
External temperature probe
AUXILIARY T-H PROBE
Addr. 129
24.0 °C
50.0 %
Status:Offline
Mask that displays the value of the serial auxiliary probe (address 129).
Visible if the probe is configured
REGULATION RAMP:
Cooling ramp: 000.0
Heating ramp: 000.0
Post Heat ramp: 000.0
FC damper ramp: 000.0
Regulation ramp punctual value reading.
SAFETY REDUCTION LOAD
NORMAL WORK
Mask that displays the status of the Safety Reduction Load function