2.7.3
Parameter Table
The numbering of the parameters is divided by menu.
•
1x corresponds to a submenu of the
“Factory menu”
•
2x corresponds to a submenu of the
“Service menu”
•
30 corresponds to a submenu of the
“User” menu
.
•
50 corresponds to the
“Setpoint” menu
.
The following table lists the controller parameters and the relative maximum and minimum values.
N. Par. Description
Default
U.M.
Min.
Max.
10.10
Internal fan project speed
70
%
0
100
10.16
Start scale value of differential pressure transducer
0
Pa
0
1000
10.17
End scale value of differential pressure transducer
100
Pa
0
5000
10.30
Start scale value of low pressure transducer
0.0
bar
0.0
2.0
10.31
End scale value of low pressure transducer
30.0
bar
0.0
10.0
10.22
Initial logo [Mitsubishi - RC]
5
-
0
5
10.26
High part serial number of unit
32
-
1
999
10.27
Medium part serial number of unit
0
-
0
999
10.28
Low part serial number of unit
0
-
0
999
10.32
Number of PAC-IF013B-E
1
-
1
2
10.33
Minimum Mr. Slim OFF time
120
S
1
999
11.01
Configuration of air flow control type [0: Disabled | 1: Flow | 2: DeltaP]
0
-
0
2
11.02
Number of EC fans
1
-
1
5
11.03
EC fan diameters [0: dn355 | 1: dn500 | 2: dn630 | 3: dn500PL | 4: dn310 Vpro-ZH | 5: dn500 Vpro-ZH | 6:
dn560 Vpro-ZH | 7: dn630 Vpro-ZH | 8: dn630PL | 9: dn710 Cpro-ZH | 10: dn255 | 11: dn310 | 12: dn400 |
13: dn450 | 14: dn560]
0
-
0
14
12.01
Minimum compressor ON time
60
s
60
600
12.02
Minimum compressor OFF time
60
s
60
600
12.03
Minimum time between two ON's of the same compressor
360
s
360
999
13.05
Electronic valve configuration [0: Disabled | 1: Enabled]
0
-
0
1
14.03
Sensors alarm delay
60
s
5
999
14.04
Low pressure alarm delay
180
s
2
999
14.08
Constructor cold setpoint minimum limit
10.0
°C
10.0
30.0
14.09
Timed dehumidification control enable [0: Disabled | 1: Enabled]
0
-
0
1
14.10
Minimum settable room temperature value for disabling dehumidification
22.0
°C
18.0
30.0
14.11
Maximum dehumidification cycle ON time
10
min
5
15
14.12
Minimum delay for new dehumidification cycle
3
min
3
20
14.13
Enabling of air flow reduction in dehumidification for direct expansion unit with dehumidification active
0
-
0
1
14.14
Maximum manual operation time
1800
s
0
3600
20.01
Regulation probe configuration [0: Return | 1: Delivery]
1
-
0
1
20.02
Fan start delay after power on
0
s
0
999
20.03
Ventilation modulation start delay
120
s
0
500
20.04
Ventilation adjustment start delay
50
s
20
999
20.06
Integral adjustment time (units with inverter)
900
s
0
999
20.07
Inverter compressor adjustment derivative time (unit with inverter)
0
s
0
999
20.08
Dirty filter sensor configuration [0: Disabled | 1: Enabled]
0
-
0
1
20.09
Smoke sensor configuration [0: Disabled | 1: Enabled]
0
-
0
1