Mask of the terminal
Description
N. Par.
DIGITAL OUTPUT STATUS:
NO1 NO8
NO2
NO3
NO4
NO5
NO6
NO7
Displays the status of the digital outputs. The number of outputs displayed depends on the type of unit.
For the meaning of each digital output,
please refer to the “input/output configuration tables”
ANALOG INPUT STATUS:
U1:00.0 bar
U2:00.0 °C
U3:00.0 °C
U4:00.0 bar
U5:
Displays the status of the universal inputs. The number of displayed inputs depends on the unit type.
For the meaning of each universal input, please refer to the “input/output configuration tables”
ANALOG OUTPUT STATUS:
Y1: 00.0V Y2: 00.0V
Y3: 00.0V Y4: 00.0V
Displays the status of the analogue outputs. The number of outputs displayed depends on the type of unit.
For the meaning of each analogue ou
tput, please refer to the “input/output configuration tables”
Input/Output GSM modem
Status:
Stand-by ext.modem
Offline 000%
Timelnextncallr:00000s
SMS Queue: 00
GSM
modem
status display mask.
Visible if the GSM modem is present and configured
Setpoint
Access mask to Setpoint menu.
Press "Up" or "Down" to scroll through the other masks and "Esc" to return to the menu selection list.
Submenu used to change the working point.
Active set point
Set point cooling:
24.0 °C
Set point heating:
00.0 °C
Active set point display mask
--------------- P50.01
Set point cooling:
24.0 °C
--------------- P50.02
Set point heating:
24.0 °C
Parameters for setting
Cold setpoint
Hot setpoint, if the hot sources enabled
50.01
50.02
--------------- P50.03
Set point dehumidif.
55%RH
--------------- P50.04
Set point humidif.:
45%RH
Parameters for setting
Dehumidification setpoint
Humidification setpoint
50.03
50.04
--------------- P50.05
Set point cooling by
LAN limits: 30.0°C
--------------- P50.06
Set point heating by
LAN limits: 18.0°C
Parameters for setting
Cold setpoint for LAN limits
Hot setpoint for LAN limits
50.05
50.06