3. Procedures
*
Precautions for starting replacement
•
Check that the main power supply is OFF.
•
Check that no refrigerant is in the outdoor unit.
Remove each part according to the 1)-3) procedures on the figure above right before replacing service parts.
Mount the removed parts back in place in a reversed procedure of 1)-3) on the figure next page after replacing
service parts.
(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement procedures
• To remove Solenoid valve block ASSY
Remove the Solenoid valve block coil cover, Solenoid valve coil, and peripheral cables.
Remove the screw (M5) that fixes the supporting plate for Solenoid valve block and the unit base.
Debraze A-F parts (total 6 places).
Do not damage heat exchanger fins and peripheral piping devices when removing the Solenoid valve block ASSY.
Remove the screw (M5) that fixes the Solenoid valve block and the supporting plate for Solenoid valve block.
• To install Solenoid valve block ASSY
Remove the pipe from the brazed G part.
Fix the Solenoid valve block ASSY and the supporting plate with the fixing screw (M5).
Mount the Solenoid valve block ASSY replacement to the unit with care not to damage heat exchanger fins and
peripheral piping devices. Fix the supporting plate for Solenoid valve block and the unit base with the fixing screw (M5).
Braze A-F parts (total 6 places).
Mount the Solenoid valve block coil cover, Solenoid valve coil, and peripheral cables back in place.
*
Precautions for replacing Solenoid valve block ASSY
•
Be sure to perform no-oxidation brazing when brazing.
•
Place a wet towel on the Solenoid valve block when heating pipes to keep the temperature of the valve
from exceeding 120ºC.
•
After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air inside.
•
Perform brazing with care of the flame direction so that it does not burn cables and plates etc. in the unit.
•
Remove the brazing part protecting heat exchanger from burning, and replace the service parts.
2
1
3
4
5
6
7
8
9
10
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...