[8-10 Troubleshooting Inverter Problems ]
- 342 -
HWE1314A
GB
8-10-9
Checking the Fan Inverter for Damage at No Load
Items to be checked
Phenomena
Remedy
(1)
Turn off breaker.
*Turn power off without fail.
1)
Within 30 seconds from the start of
operation, an error other than a posi-
tion error (5305, 5306) (detail code
132) is detected.
Change fan board.
(2)
Disconnect the connector
CNINV from the fan board.
2)
Less than 5V unbalance in the wir-
ing.
Change fan board.
(3)
Set fan board switch SW1-1 to
ON.
3)
No unbalanced voltage in the wiring.
After 30 second, detail code 132 is
produced and the system stops.
Normal
*After checking, return
SW1&CNINV.
(4)
Turn on breaker.
(5)
Operate unit.
After about 30 seconds under
no load with constant voltage
output, the code below will be
displayed indicating a position
error (5305, 5306).
Detail code: 132
Also, running with no load pro-
duces constant voltage of
about 160V.
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...