[8-8 Troubleshooting LEV Problems ]
- 325 -
HWE1314A
GB
8
Trou
ble
sho
oting
Bas
ed
on
Obse
rved
Sy
mpto
ms
8-8-3
Coil Removal Instructions
(1) Outdoor unit LEV (LEV5a and 5b)
1) Components
The outdoor unit LEV consists of a coil and a valve body that can be separated from each other.
2) Removing the coil
Securely hold the LEV at the bottom (as indicated by A in the figure), and turn the coil. After checking that the stopper is re-
moved, pull up and out the coil.
When removing the coil, hold the LEV body securely to prevent undue force from being placed on the pipe and bending the
pipe.
3) Installing the coil
Securely hold the bottom of the LEV (section A in the figure), insert the coil from above, and turn the coil until the coil stopper
is properly installed on the LEV body.
When removing the coil, hold the LEV body securely to prevent undue force from being placed on the pipe and bending the
pipe.
Stopper
Lead wire
Coil
Body
Part A
Stopper
Stopper
Part A
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...