[3-7 Functions of the Major Components of BC Controller ]
- 92 -
HWE1314A
GB
(5) HB1 type
Part name
Symbols
(functions)
Part
code
Usage
Specifications
Check method
Thermistor TH12
(Bypass
outlet tem-
perature)
LEV control (Superheat)
0°C[32°F] : 15 kΩ
10°C[50°F] :9.7 kΩ
20°C[68°F] :6.4 kΩ
25°C[77°F] :5.3 kΩ
30°C[86°F] :4.3 kΩ
40°C[104°F] :3.1 kΩ
TH15
(Bypass in-
let tempera-
ture)
LEV control (Superheat)
Solenoid
valve
SVA
Provides refrigerant to indoor
unit in cooling operation
AC220-240V
Open while being powered/
closed while not being pow-
ered
Continuity
check with a
tester
SVB
Provides refrigerant to indoor
unit in heating operation
SVC
Provides refrigerant to indoor
unit in cooling operation
LEV
LEV3
Pressure differential control
DC12V
Opening of a valve driven by a
stepping motor
0-2000 pulses
Same as
indoor LEV
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...