[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 263 -
HWE1314A
GB
7
Troub
le
sho
oting
Using
Erro
r Cod
es
7-7-15
Error Codes [5305, 5306] Detail Code 134
1. Error code definition
RPM error before start up (Detail code 134)
2. Error definition and error detection method
The fan RPM will not drop to the set RPM.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
7-7-16
Error Code [5701]
1. Error code definition
Loose float switch connector
2. Error definition and error detection method
Detection of the disconnected float switch (open-phase condition) during operation
3. Cause, check method and remedy
(1) CN4F disconnection or contact failure
Check for disconnection of the connector (CN4F) on the indoor unit control board.
Cause
Check method and remedy
(1)
Outdoor factors
Check that there is no wind (gust or strong wind).
(2)
Fan board failure
Refer to the following page(s).
[8-10-9 Checking the Fan Inverter for Damage at No Load](page 342)
[8-10-10 Checking the Fan Inverter for Damage with Load](page 343)
(3)
Fan motor error
Refer to the following page(s).
[8-10-7 Checking the Fan Motor for Ground Fault and Coil Resis-
tance Problems](page 341)
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...