[8-11 Control Circuit ]
- 352 -
HWE1314A
GB
2) PURY-EP500YLM-A
YES
YES
YES
NO
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
NO
YES
YES
NO
NO
NO
YES
YES
YES
NO
YES
NO
A
B
C
YES
Check the voltage between No.1 and No.2 pins of the
CNS2 on the control board.
Check the wiring between the control board and M-NET board
for the transmission line (CN62, CNPS, CN102 and CNIT),
and check for proper connection of connectors.
Check the wiring between the control board and M-NET board
for the transmission line (CN62, CNPS, CN102 and CNIT),
and check for proper connection of connectors.
Is there a wiring
error or a connector
disconnection?
Check the voltage between No.5 and No.2 pins of
the CNPS on the control board.
Is the voltage
measurement between
4.5 and 5.2 VDC?
Is there a connector
disconnection?
Fix the connector disconnection.
Replace the M-NET board
Replace the control board.
Replace the M-NET board
Replace the noise filter.
Connect the noise filter CN104, and then turn the power on.
Connect the capacitor board CN107, and then turn the power on.
Disconnect the capacitor board CN103, CN104 and CN107,
and then replace F3, then turn the power on.
Fix the wiring and connector
disconnection.
Check for shorted transmission
line or power feed collision for
centralized control.
Replace the control board.
Check the voltage between No.1 and No.2 pins of the
CN102 on the M-NET board for the transmission line.
Check the voltage between No.1 and No.4 pins of the
CN104 on the
capacitor board
for the transmission line.
Check the voltage between No.1 and No.3 pins of
the noise filter CN103.
Check the noise filter F3 fuse.
Check the voltages among TB23 and TB24 on the
noise filter.
24 ~ 30 V
DC
24 ~ 30 V
DC
279 ~ 374 V
DC
279 ~ 374 V
DC
F3 blown
F3 blown
F3 blown
F3 blown
Check the voltage at the indoor/outdoor
transmission terminal block (TB3) of outdoor unit.
24 ~ 30 VDC
24 ~ 30 VDC
24 ~ 30 VDC
24 ~ 30 VDC
Check the voltage at TB3 after removing transmission line from TB3.
Check whether the male connector is connected to
the female power supply connector (CN40).
Connected
Check voltage of terminal block for centralized control (TB7).
Check voltage of TB7 by removing transmission line from TB7.
Check if the indoor/outdoor transmission line is not
short-circuited, and repair the problem.
Check whether the transmission line is disconnected,
check for contact failure, and repair the problem.
Replace the control board.
Replace the inverter board.
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...