[5-2 Outdoor Unit Control ]
- 137 -
HWE1314A
GB
5
Cont
rol
(4) Bypass solenoid valve (SV7) (ON = Open)
(5) Bypass solenoid valve (SV10) (ON = Open)
(6) Bypass solenoid valve (SV11) (ON = Open)
Operation
SV7
During heating operation or during heating-
main operation
ON
During defrost cycle
OFF
When stopped
OFF
Others
OFF
Operation
SV10
When defrosting upper heat exchanger dur-
ing Continuous heating mode(P200 to P400
models and EP200 to EP350 models)
When defrosting left heat exchanger during
Continuous heating mode
(P450 to P500 models and EP400 to EP500
models)
ON
Others
OFF
Operation
SV11
When defrosting lower heat exchanger dur-
ing Continuous heating mode
(P200 to P400 models and EP200 to EP350
models)
When defrosting right heat exchanger dur-
ing Continuous heating mode
(P450 to P500 models and EP400 to EP500
models)
ON
Others
OFF