[5-3 BC Controller Control ]
- 152 -
HWE1314A
GB
5-3
BC Controller Control
1. Control of SVA, SVB, and SVC
SVA, SVB, and SVC turn on or off depending on the operation mode of the branch.
2. Control of SVM1 snd SVM1b
SVM turns on or off depending on the operation mode.
3. Control of LEV
LEV opening (sj) is controlled as follows depending on the operation mode.
4. Control of SVM2, and SVM2b
Mode
Cooling
Heating
Stopped
Defrost
Port
SVA
ON
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
SVC
ON
OFF
OFF
OFF
Operation
mode
Cooling only Cooling main Heating only Heating main
Defrost
Stopped
SVM1,1b
ON
Pressure dif-
ferential con-
trol
*1
*1. Pressure differential control: The detected differential pressure (PS1 and PS3) is controlle every minute
so as to be within a certain range.
OFF
OFF
ON
OFF
Operation mode
Cooling only
Cooling
main
Heating only
Heating
main
Defrost
Stopped
G1,GA1
HA1
type
LEV1
2000
Liquid level
control
*1
dif-
ferential
control
*2
*1. Liquid level control: The liquid level detected by the liquid inlet temperature (TH11 sensor) is controlled so as to be within
a certain range.
*2. Pressure differential control: The detected differential pressure (PS1 and PS3) is controlle every minute so as to be within
a certain range.
110
110
*3
*3. Can be 110 or more due to pressure rise on the liquid side (PS1).
2000
1200
LEV3
Superheat
control
*4
*4. Superheat control: The amound of superheat that is calculated on the bypass inlet and outlet temperature (TH12, TH15)
is controlled every minute so as to be within a certain range.
Pressure dif-
ferential con-
trol
*2
Pressure dif-
ferential con-
trol
*2
G1:1000
GA1,HA1:2000
60
GB1,HB1
type
LEV3
Superheat
control
*4
Superheat
control
*4
60
60
60
60
Operation
mode
Cooling only
Cooling main
Heating only
Heating main
Defrost
Stopped
SVM2,2b
OFF
OFF
Pressure differ-
ential control
*1
*1. Pressure differential control: The detected differential pressure (PS1 and PS3) is controlled every minute so as to be
within a certain range.
Pressure differ-
ential control
*1
OFF
OFF
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...