[8-15 BC Controller Maintenance Instructions ]
- 379 -
HWE1314A
GB
8
Trou
ble
sho
oting
Bas
ed
on
Obse
rved
Sy
mpto
ms
3. Thermistor (liquid pipe/gas pipe temperature detection)
4. Pressure sensor
*Special care must be taken when replacing heavy parts.
Work procedure
Explanatory figure
(1) Remove the service panel.
1) For TH11, TH12, and TH15, refer to 1. 1), 2).
2) For TH16, refer to 1. 1), 2), 3). (GA1 type only)
(2) Remove the lead wire of the piping sensor from the
control board.
1) TH11,TH12 (CN10)
2) TH15,TH16 (CN11)
(3) Pull out the temperature sensor from the tempera-
ture sensor housing, and replace the temperature
sensor with the new one.
(4) Connect the lead wire of the temperature sensor se-
curely on the control board.
CMB-1016V-GA1
Work procedure
Explanatory figure
(1) Remove the service panel.
1) For the pressure sensors PS1 and PS3, refer to 1. 1), 2).
(2) Remove the pressure sensor connector in trouble
from the control board, and insulate the connector.
1) Liquid-side pressure sensor (CNP1)
2) Intermediate-part pressure sensor (CNP3)
(3) Attach a new pressure sensor to the place which is
shown in the figure, and insert the connector to the
control board.
When gas leaks from the pressure sensor, repair the
leak, and follow the instructions above if required.
TH15
TH12
TH16
TH11
SVM1
PS1
PS3
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...