[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 262 -
HWE1314A
GB
7-7-13
Error Codes [5305, 5306] Detail Code 132
1. Error code definition
Position detection error at startup (Detail code 132)
2. Error definition and error detection method
When a motor sensor has detected an error within 10 seconds after the fan motor has gone into operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
7-7-14
Error Codes [5305, 5306] Detail Code 133
1. Error code definition
Position detection error during operation (Detail code 133)
2. Error definition and error detection method
An error from a motor sensor is detected during fan moter operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
Cause
Check method and remedy
(1)
Contact failure and faulty fan motor
wiring
Check the fan board connector CNINV and CNSNR for proper con-
tacts.
Check the wirign betweem the fan motor and fan board.
(2)
Fan board failure
Refer to the following page(s).
[8-10-10 Checking the Fan Inverter for Damage with Load](page 343)
(3)
Fan motor error
Refer to the following page(s).
[8-10-7 Checking the Fan Motor for Ground Fault and Coil Resis-
tance Problems](page 341)
Cause
Check method and remedy
(1)
Outdoor factors
Check that there is no wind (gust or strong wind).
(2)
Contact failure and faulty fan motor
wiring
Check the fan board connector CNINV and CNSNR for proper contacts.
Check the wirign betweem the fan motor and fan board.
(3)
Fan board failure
Refer to the following page(s).
[8-10-9 Checking the Fan Inverter for Damage at No Load](page 342)
[8-10-10 Checking the Fan Inverter for Damage with Load](page 343)
(4)
Fan motor error
Refer to the following page(s).
[8-10-7 Checking the Fan Motor for Ground Fault and Coil Resistance
Problems](page 341)
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...