[5-2 Outdoor Unit Control ]
- 146 -
HWE1314A
GB
5-2-13
Emergency Operation Mode
1. Problems with the outdoor unit
Systems with two outdoor units have a mode that allows one of the outdoor units to perform a backup operation when the
other outdoor unit in the system malfunctions.
This mode can be started by performing an error reset via the remote controller.
(1) Starting the emergency operation
1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller.
2) The error is reset using the remote controller.
3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation
starts.
4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting
the error via the remote controller.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Emergency operation pattern (2 outdoor units)
1) If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable ca-
pacity, some of the indoor units will go into the same condition as Thermo-OFF.
Trouble source
Error codes that permit an
emergency operation
Error code description
Compressor
Fan motor
Inverter
0403
Serial communication error
4220,4225,4226
Bus voltage drop
4230,4235
Heatsink overheat protection
4240,4245
Overload protection
4250,4255,4256
Overcurrent relay trip
5110
Heatsink temperature sensor failure (THHS)
5301
Current sensor/circuit failure
5305,5306
Position error
Thermistor
TH2
5102
Subcool heat exchanger bypass outlet temperature sensor failure
TH3
5103
Pipe temperature sensor failure
TH4
5104
Discharge temperature sensor failure
TH5
5105
Accumulator inlet temperature sensor failure
TH6
5106
Subcool heat exchanger liquid outlet sensor failure
TH7
5107
Outside air temperature sensor failure
TH9
5109
Continuous heating temperature sensor fault
TH11
5111
Continuous heating temperature sensor fault
TH12
5112
Continuous heating temperature sensor fault
Power
4102
Open phase
4115
Power supply sync signal abnormality
OC
OC failure
pattern
Trouble
Normal
Permitted Permitted
Permitted Permitted
60%
Cooling
Heating
Normal
Trouble
OS failure
pattern
OS
Emergency
operation
Maximum total capacity
of indoor units (Note 1)
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...