[7-4 Error Code Definitions and Solutions: Codes [2000 - 2999] ]
- 236 -
HWE1314A
GB
7-4-5
Error Code [2503]
1. Error code definition
Drain sensor (Thd) fault
2. Error definition and error detection method
If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary
error, and the unit goes into the 3-minute restart delay mode.
If another episode of the above condition is detected during the preliminary error, this is considered a drain sensor error.(If
the short or open circuit of the thermistor is no longer detected, normal operation will be restored in 3 minutes.)
This error is detected when one of the following conditions are met.
During Cool/Dry operation
Liquid pipe temperature minus inlet temperature is equal to or smaller than - 10°C [ -18°F] (except during the defrost cycle)
When the liquid temperature thermistor or suction temperature thermistor or short or open circuited.
Drain pump is in operation.
One hour has elapsed since the drain sensor went off.
Short: 90°C [194 °F] or above
Open: - 20°C [-4 °F] or below
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Faulty connector (CN31) insertion.
1) Check for connector connection failure.
Reinsert the connector, restart the operation, and check for
proper operation.
(2)
Broken or semi-broken thermistor wire
2) Check for a broken thermistor wire.
(3)
Thermistor failure
3) Check the resistance of the thermistor.
0°C[32 °F]:6.0 kΩ
10°C[50 °F]:3.9 kΩ
20°C[68°F]:2.6 kΩ
30°C[86°F]:1.8 kΩ
40°C[104 °F]:1.3 kΩ
(4)
Indoor unit control board (error detection circuit)
failure
4) Replace the indoor unit control board if the problem recurs
when the unit is operated with the No.-1 and No.-2 pins on
the drain sensor connector (CN31) being short-circuited.
If the above item checks out OK, there are no problems with
the drain sensor.
Turn off the power and turn it back on.
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...