[2-10 Restrictions on Refrigerant Pipes ]
- 58 -
HWE1314A
GB
7) The maximum capacity of the indoor units that is connectable to the CMB-P-V-GB1 types of sub BC controllers is P350 or
below (when two GB1 type controllers are connected P350 or below for both combined) .
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016V-HB1 is P350 or below.
If at least one CMB-P1016V-HB1 unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P450 or below.
Restrictions on pipe length
[PURY-(E)P200, 250YLM]
[PURY-(E)P300, 350, 400, 450, 500YLM]
[PURY-P400, 450YSLM, (E)P500, 550YSLM]
[PURY-(E)P600, 650YSLM]
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
[PURY-(E)P700, 750, 800, 850, 900YSLM]
200
300
400
500
600
700
800
900
1000
10 20 30 40 50 60 70 80 90 100 110
Distance between outdoor unit and BC controller(m)
Total
extended
pipe
length
(m)
0
10
20
30
40
50
60
70
0
5
10
15
Piping length between the main
BC controller and indoor units (m[ft])
Vertical separation between the main BC controller and indoor units (m[ft])
The height difference and the pipe length between BC controller and indoor units
[32]
[16]
[32]
[49]
[64]
[98]
[131]
[164]
[196]
[229]
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...