[6-11 Standard Operation Data (Reference Data) ]
- 203 -
HWE1314A
GB
6
T
est
Ru
n
6-11-3
Single Unit (High COP Unit)
Outdoor unit model
PURY-EP200YLM-A
PURY-EP250YLM-A
BC controller model
CMB-P104V-G1
CMB-P104V-G1
Conditions
Ambient temperature
(cooling)
Indoor
DB/WB
27°C/19°C [81°F/66°F]
27°C/19°C [81°F/66°F]
Outdoor
35°C/- [95°F/-]
35°C/- [95°F/-]
Ambient temperature
(heating)
Indoor
DB/WB
20°C/- [68°F/-]
20°C/- [68°F/-]
Outdoor
7°C/6°C [45°F/43°F]
7°C/6°C [45°F/43°F]
Indoor unit
Number of units connected
Unit
2
2
Number of units in operation
2
2
Model
-
100/100
125/125
Piping
Main pipe
m [ft]
5
[16-3/8"]
5
[16-3/8"]
Branch pipe
10
[32-3/4"]
10
[32-3/4"]
Total pipe length
25
[82]
25
[82]
Fan speed
-
Hi
Hi
Refrigerant charge
kg [lbs-oz]
16.3
[35-15]
18.0
[39-11]
Outdoor unit
Voltage
V
400
400
Cooling-Only
Outdoor unit
Electric current
A
8.7
11.6
Compressor frequency
Hz
52
65
LEV open-
ing
Indoor unit
Pulse
325/325
387/387
BC controller (1/2/3)
2000/-/180
2000/-/170
Pressure
High pressure (63HS1)/Low pressure (63LS)
MPa [psi]
2.67/0.97 [387/141]
2.82/0.99
[409/144]
BC controller on the liquid side (PS1)/Mid-way point (PS3)
2.60/2.60 [377/377]
2.74/2.74
[397/397]
Section
tempera-
tures
Outdoor unit
Discharge (TH4)
°C [°F]
76
[169]
87
[189]
Heat exchanger outlet (TH3)
41
[106]
41
[106]
Accumulator inlet
14
[57]
8
[46]
Accumulator outlet
14
[57]
8
[46]
Compressor inlet
23
[73]
19
[66]
Compressor shell bottom
34
[93]
40
[104]
Indoor unit
LEV inlet
24
[75]
19
[66]
Heat exchanger inlet
12
[54]
6
[43]
Heating-Only
Outdoor unit
Electric current
A
10.2
13.5
Compressor frequency
Hz
53
71
LEV open-
ing
Indoor unit
Pulse
332/332
406/406
BC controller (1/2/3)
110/-/520
110/-/590
Pressure
High pressure (63HS1)/Low pressure (63LS)
MPa [psi]
2.33/0.7
[338/102]
2.32/0.64
[336/93]
BC controller on the liquid side (PS1)/Mid-way point (PS3)
2.26/2.00 [328/290]
2.28/2.00
[331/290]
Section
tempera-
tures
Outdoor unit
Discharge (TH4)
°C [°F]
68
[154]
78
[172]
Heat exchanger inlet (TH6)
2
[36]
0
[32]
Accumulator inlet
1
[34]
-2
[28]
Accumulator outlet
1
[34]
-3
[27]
Compressor inlet
1
[34]
-3
[27]
Compressor shell bottom
40
[104]
40
[104]
Indoor unit
LEV inlet
30
[86]
36
[97]
Heat exchanger inlet
62
[144]
68
[154]
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...