[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 240 -
HWE1314A
GB
7-6-2
Error Code [4106]
1. Error code definition
<Transmission power supply fault Error detail code FF (Outdoor unit)>
2. Error definition and error detection method
Transmission power output failure
3. Cause
1) Wiring failure
2) Transmission power supply cannot output voltage because overcurrent was detected.
3) Voltage cannot be output due to transmission power supply problem.
4) Transmission voltage detection circuit failure
4. Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems. [8-11-2 Trouble-
shooting Problems with Outdoor Unit Transmission Power Supply Circuit](page 351)
1. Error code definition
<Transmission power supply fault other than error detail code FF (Outdoor unit)>
2.Error definition and error detection method
Transmission power reception failure
3.Cause
One of the outdoor units stopped supplying power, but no other outdoor units start supplying power.
4.Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems. [8-11-2 Trouble-
shooting Problems with Outdoor Unit Transmission Power Supply Circuit](page 351)
7-6-3
Error Code [4109]
1. Error code definition
Indoor unit fan operation error
2. Error definition and error detection method
1) Connector CN28 has remained open-circuited for 100 consecutive secondsduring operation.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Auxiliary relay (X13) fault
The coil or the wiring of the auxiliary relay connected to
CN28 is faulty.
(2)
Connector (CN28) is disconnected.
Check the connector for proper connection.
(3)
Blown fuse
Check the fuse on the control circuit board.
(4)
Motor error (thermistor error inside the motor)
Check the unit fan for proper operation in the test run
mode.
If no problems are found with items 1 through 3 above and
the fan does not operate, replace the motor.
Summary of Contents for PURY-EP200YLM-A
Page 9: ...viii ...
Page 13: ... 2 HWE1314A GB ...
Page 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Page 31: ... 20 HWE1314A GB ...
Page 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Page 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Page 77: ... 66 HWE1314A GB ...
Page 105: ... 94 HWE1314A GB ...
Page 137: ... 126 HWE1314A GB ...
Page 171: ... 160 HWE1314A GB ...
Page 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Page 231: ... 220 HWE1314A GB ...
Page 395: ... 384 HWE1314A GB ...