6 INSTALLATION AND EXTERNAL WIRING
6.2 External Wiring
43
6
Interface with external devices
The following table shows the interface of the flexible high-speed I/O control module with external devices.
Electrical specifications of external I/O signals
■
External input signal
The following table shows the input specifications of the flexible high-speed I/O control module.
*1 When the filter time has been set to 0
μ
s
■
External output signal
The following table shows the output specifications of the flexible high-speed I/O control module.
Signal name
Operation
Input voltage
(Guaranteed value)
Operating current
Response time
24VDC input
On
21.6 to 26.4V
4 to 6mA
1
μ
s
Off
5V or less
1.0mA or less
5VDC input
On
4.5 to 5.5V
4 to 8mA
1
μ
s
Off
2V or less
1.0mA or less
Differential input
Equivalent to AM26C32
1
μ
s
Signal name
Item
Description
DC output
Operating load voltage
4.75 to 30VDC
Maximum load current
0.1A/point
Maximum voltage drop at ON
0.5V
Response time
OFF
→
ON
1
μ
s or less (Rated load, resistive load)
ON
→
OFF
1
μ
s or less (Rated load, resistive load)
Differential output
Operating load voltage
Equivalent to AM26C31
Maximum load current
Maximum voltage drop at ON
Response time
1
μ
s or less
Summary of Contents for MELSEC-L Series LD40PD01
Page 2: ......
Page 9: ...7 MEMO ...
Page 24: ...22 2 PART NAMES MEMO ...
Page 35: ...4 PROCEDURES BEFORE OPERATION 33 4 MEMO ...
Page 263: ......