10 BLOCK LINK EXAMPLES
10.3 Event Generation
183
10
■
Multi function counter block detail window
Operation
The following shows operation where the input signal 1 turns to High when a rise of the input signal 0 is detected.
Block
Variable name
Setting value
Description
Input 0
Input 1
Input_Signal_Event
Detector Select
User Setting (ON only in A: Rise)
Set conditions to generate an event signal.
Detector Select
User Setting (ON only in B: High)
Event 0
Event 2
No.
Description
(1)
When a rise of the input terminal 0 is detected, the event output terminal 0 turns to High and to Low.
(2)
When a rise of the input terminal 1 is detected, the event output terminal 2 turns to High.
(3)
When a fall of the input terminal 1 is detected, the event output terminal 2 turns to Low.
High
Low
(3)
High
Low
(2)
High
Low
High
Low
(1)
Event output terminal 0
Event output terminal 2
Input terminal 1
Controlled by the flexible high-speed I/O control module
Input terminal 0