10 BLOCK LINK EXAMPLES
10.2 One-shot Timer
179
10
■
Multi function counter block detail window
*1 Output ON time = Clock cycle setting
×
(Compare value - Preset value + 1)
*2 In the addition mode, the output ON time calculated from the following is applied.
Output ON time = (Clock cycle setting
×
(Compare value - Preset value + 1)
÷
Addition value
The items other than the above need not to be set.
Block
Variable name
Setting value
Description
Input 0
Input_Signal_Event
Detector Select
User Setting (ON only in A: High)
Set this parameter to detect the phase A input signal.
Detector Select
User Setting (ON only in A: Rise)
Counter_Timer_0
Count Enable
ON
Set this parameter to "ON".
Count Mode
Linear
Set this parameter according to the control.
Upper Limit
4294967295
Set this parameter according to the control.
Lower Limit
0
Set this parameter according to the control.
Clock
1ms
Set this parameter according to the control.
Add Mode
OFF
Set this parameter according to the control.
Add Value
0
STOP
→
PRESET
ON
Set this parameter to "ON", to perform a preset when
a stop event occurs.
PRESET
→
STOP
OFF
Set this parameter to "OFF".
Preset Value
1
Set this parameter according to the control.
Compare_0
Condition
Coincidence
Set this parameter to "Coincidence".
Compare Mode A
=
Set this parameter to "=".
Compare Value A
100
Set this parameter according to the control.
Set/Reset_0
Output