10 BLOCK LINK EXAMPLES
10.6 Fixed Cycle Output
191
10
■
Multi function counter block detail window
*1 Cycle time = (Upper limit value - Lower limit value)
×
Clock cycle
*2 In the addition mode, the cycle time calculated from the following is applied.
Cycle time = (Upper limit value - Lower limit value)
÷
Addition value
×
Clock cycle
However, when the count value and the setting value of Step No. 0 do not match each other with the set addition value, fixed cycle
pulses are not output.
The items other than the above need not to be set.
Block
Variable name
Setting value
Description
Input 0
Input 1
Event 0
Event 1
Input_Signal_Event
Detector Select
User Setting
(ON only in A: Rise)
Set conditions to detect a fixed cycle output start
signal.
Detector Select
User Setting
(ON only in B: Rise)
Set conditions to detect a fixed cycle output stop
signal.
Counter_Timer_0
Count Enable
ON
Set this parameter to "ON".
Count Mode
Ring
Set this parameter to "Ring".
Upper Limit
1000
Set this parameter according to the control.
Lower Limit
0
Set this parameter according to the control.
Clock
1ms
Set this parameter according to the control.
Add Mode
OFF
Set this parameter according to the control.
Add Value
0
STOP
→
PRESET
ON
Set this parameter to "ON", to perform a preset when
a stop event occurs.
Preset Value
0
Set the same value as that in "Lower Limit".
Cam Switch
Number of Step
1
Set "1" to enable the step No. 0.
Lower Limit Output State
Low
Set this parameter to "Low".
Step No.0
999
Set a value of "Upper limit value of the counter timer
block - 1".
Cam Output