9 CREATING A HARDWARE LOGIC
9.2 Multi Function Counter Block
■
When the number of steps is set to 2
• Setting details
*1 Set it in the counter timer block.
*2 When "Low" is set, operations of output within the range are performed. When "High" is set, operations of output out of the range are
executed.
• Operation
Setting method
Set the cam switch block with the following procedure.
1.
Set the number of steps of the cam switch for "Number of Step".
2.
Set "Step No.0" to "Step No.15" so that the setting values in "Lower Limit", "Step No.0" to "Step No.15", and "Upper Limit"
are arranged in ascending order.
When the setting values in "Lower Limit", "Step No.0" to "Step No.15", and "Upper Limit" are not arranged in
ascending order, the control for the cam switch block is not normally performed.
Item
Setting value
Number of Step
2
-2147483648
Lower Limit Output State
Low
Step No.0
1000
Step No.1
2000
Upper Limit
2147483647
No.
Description
(1)
For "Lower Limit"
≤
Count value < "Step No.0", the output status set with "Lower Limit Output State" is applied.
When the count value is equal to or larger than the set value of "Step No.0", the output status turns to High.
(2)
When the count value is equal to or larger than the set value of "Step No.1", the output status turns to Low.
ON
OFF
0
(1)
(2)
1
1000
2000
Step No.
"Output" terminal
"Count Value"