10 BLOCK LINK EXAMPLES
10.4 Cam Switch
185
10
■
Multi function counter block detail window
The items other than the above need not to be set.
Block
Variable name
Setting value
Description
Input 0
Input 1
Input_Signal_Event
Detector Select
2-phase multiple of 1+
Set this parameter to detect an addition pulse.
Detector Select
2-phase multiple of 1-
Set this parameter to detect a subtraction pulse.
Counter_Timer_0
Count Enable
ON
Set this parameter to "ON".
Count Mode
Ring
Set this parameter according to the control.
Upper Limit
10000
Set this parameter according to the control.
Lower Limit
0
Set this parameter according to the control.
Clock
25ns
Set this parameter to "25ns". (to prevent input pulses
from missing)
Add Mode
OFF
Set this parameter according to the control.
Add Value
0
Cam Switch
Number of Step
7
Set "7", which is the number of steps of the cam
switch, to enable the step No. 0 to 6.
Lower Limit Output State
Low
Set this parameter according to the control.
Step No.0
1000
Set a count value at which the output status of the
subsequent step is enabled.
Step No.1
2000
Step No.2
3000
Step No.3
4000
Step No.4
5000
Step No.5
6000
Step No.6
7000
Cam Output