8 APPLICATION INSTRUCTION
8.17 Pulse Related Instruction
623
8
Operation error
Error code
(SD0/SD8067)
Description
1810H
The output destination specified by (d) is already used by another instruction (positioning instruction).
(The PWM output is not executed.)
A Y device is specified as the output destination specified by (d), and there is no unused channel number in the parameter setting
3405H
Y10 or later is specified as the output destination specified by (d).
(The PWM output stops.)
3580H
An instruction that cannot be used in an interrupt program is used.
3600H
A channel number that is not selected in the parameter setting are specified for the output destination specified by (d).
(The PWM output is not executed.)
3611H(CH1)
3612H(CH2)
3613H(CH3)
3614H(CH4)
3615H(CH5)
3616H(CH6)
3617H(CH7)
3618H(CH8)
3619H(CH9)
361AH(CH10)
361BH(CH11)
361CH(CH12)
The ON time specified by (s1) is larger than the period specified by (s2).
(The PWM output stops.)
In (s1) and (s2), a negative value is specified.
(The PWM output stops.)
Values of an SD device for setting pulse width and period of this instruction are incorrect.
(The PWM output stops.)
The ON time or period is less than “1”.
The SD device specified for the number of output pulses stores a value outside the available range (0 to 2147483647).
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......