6 SEQUENCE INSTRUCTIONS
6.3 Output Instructions
135
6
Precautions
• When write during RUN is completed for a circuit including a falling edge instruction (LDF/ANDF/ORF instruction), the
instruction is not executed regardless of the ON/OFF status of the target device of the falling edge instruction. Also, in the
case of a falling edge instruction (PLF instruction), the instruction is not executed regardless of the ON/OFF status of the
device that is set as the operation condition. The instruction is executed when the target device and the device in the
operation conditions is set from ON to OFF again.
• Note that the device specified by (d) sometimes turns ON for one scan or more when the PLF instruction is made to jump
by the CJ instruction or the executed subroutine program was not called by the CALL(P) instruction.
Operation error
There is no operation error.