7 BASIC INSTRUCTIONS
7.4 Bit Processing Instructions
281
7
• As a reset instruction for individual devices, the RST instruction can be used for bit devices and word devices.
• The FMOV(P) instruction is a batch write instruction for a constant (K0 for example) that can write "0" for word devices
(including nibble specification of bit devices).
Precautions
• Specify the same type of device for (d1) and (d2) so that (d1) number is less than (d2) number. If the (d1) number
(d2)
number, only the device specified by (d1) is reset.
• The ZRST(P) instruction is a 16-bit instruction, but long counter (LC) and long index register (LZ) can be specified for (d1)
and (d2).
Operation error
(1): M0 is reset.
(2): The current value of T0 is reset.
(3): D0 is reset.
(1): K0 is written to D0 to D99.
Error code
(SD0/SD8067)
Description
2820H
The number of devices to be reset is 32768 or more when module access device has been specified for (d1) and/or (d2).
3405H
Device type specified by (d1) differs from type specified by (d2).
Module number for (d1) and (d2) differ when module access device is specified.
RST
X1
RST
RST
M0
T0
D0
(1)
(2)
(3)
FMOV
X2
K0
D0
K100
(1)
ZRST
ZRST
C180
C199
LC0 LC10
X0
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......