402
8 APPLICATION INSTRUCTION
8.4 Structuring Instruction
Operation error
[Timing chart]
A: Execution of subroutine P0 triggered by X0
Error code
(SD0/SD8067)
Description
3360H
The 17th level of the nesting is executed.
3380H
The subroutine program specified by the pointer in the CALL(P) instructions do not exist.
3381H
After the CALL(P) instructions are executed, the END, FEND, GOEND, or STOP instruction is executed before the RET (SRET)
instruction is executed.
3382H
The RET (SRET) instruction is executed before the CALL(P) instructions are executed.
X2
Y7
X1
1
2
3
1
2
3
4
RST
C0
Subroutine is executed.
A
Counter reset instruction is
deactivated (part in
above program).
Resets Y7.
B
Counter is reset
(part in above
program).
A
Current
value of
C0