8 APPLICATION INSTRUCTION
8.9 Real Number Instruction
Processing details
• These instructions convert a unit of angle from degrees (DEG.) specified by (s) into radians, and store the converted angle
in the device specified by (d).
• The conversion from degrees into radians is executed as follows:
• The table below shows the related devices.
Operation error
Device
Name
Description
Condition
Operation
SM700
Carry
The absolute value of the operation result
2
128
The value of (d) is the maximum value (2
128
) of 32-bit real
numbers and the carry flag SM700 turns on.
SM8020
Zero
The operation result is true "0".
(The mantissa part is "0").
The zero flag SM8020 turns on.
SM8021
Borrow
The absolute value of the operation result < 2
-126
The value of (d) is the minimum value (2
-126
) of 32-bit real
numbers and the borrow flag SM8021 turns on.
SM8022
Carry
The absolute value of the operation result
2
128
The value of (d) is the maximum value (2
128
) of 32-bit real
numbers and the carry flag SM8022 turns on.
Error code
(SD0/SD8067)
Description
3402H
The specified device value is -0, denormalized number, NaN (not a number), or
.
(s)+1
(s)
(d)+1
(d)
( )
( ) rad
Single-precision real number
Single-precision real number
Radians = Degrees
180
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......