6 SEQUENCE INSTRUCTIONS
6.3 Output Instructions
115
6
Timer
OUT T, OUTH T, OUTHS T, OUT ST, OUTH ST, OUTHS ST
The timer counts up to the set value when the operation result up to the OUT instruction is ON and the coil of the timer/
retentive timer specified by (d) turns ON. When the timer times up, NO contact becomes conductive and NC contact becomes
non conductive.
Setting data
■
Descriptions, ranges, and data types
*1 In the case of the ST language and the FBD/LD language, d displays as Coil.
*2 In the case of the ST language and the FBD/LD language, Set value displays as Value.
*3 Only timer type/retentive timer type label can be used.
*4 In the case of the OUT_T instruction of the ST language and the FBD/LD language , data type is ANY_INT.
■
Applicable devices
*1 Only T and ST can be used.
*2 T, ST, C cannot be used.
*3 Only decimal constant (K) can be used.
Processing details
• These instructions count up to the set value when the operation result up to the OUT instruction is ON and the coil of the
timer/retentive timer specified by (d) turns ON. When the timer reaches the end of its count (current value
set value), NO
contact becomes conductive and NC contact becomes non-conductive.
• Operation is as follows when the operation result up to the OUT instruction changes from ON to OFF.
Ladder diagram
Structured text
ENO:=OUT_T(EN,Coil,Value);
ENO:=OUTH(EN,Coil,Value);
ENO:=OUTHS(EN,Coil,Value);
FBD/LD
("OUT_T", "OUTH", "OUTHS" enters
.)
Operand
Remarks
Range
Data type
Data type (label)
(d)
Timer Number
Timer/retentive timer
ANY
(Set value)
Timer set value
0 to 32767
16-bit unsigned
binary
ANY16
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L, SM,
F, B, SB, S
T, ST, C, D, W,
SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(d)
(Set value)
Timer type
Timer coil
Current timer
value
Before time-out
After time-out
NO contact
NC contact
NO contact
NC contact
Timer
off
0
Non-Conductive
state
Conductive state
Non-Conductive
state
Conductive state
Retentive timer
off
Holds current value
Non-Conductive
state
Conductive state
Conductive state
Non-Conductive
state
(d)
Value
EN
ENO
Coil
Value
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......