22 - 4
22.1 GOT Restoration Sheets
(4) GOT restoration procedure
Follow the procedures in order from (a) and check if the GOT is restored.
If the GOT is still not restored, go to the next step.
*1
Before powering on the GOT again (OFF
ON), make sure to power off the PLC.
(5) Actual product investigation
When the GOT still operates improperly even after the corrective actions described above are taken, contact your
local distributor.
Depending on the error status, the actual product may need to be returned to us.
In that case, attach the GOT status check sheet, GOT installation status check sheet, and system configuration
check sheet (Write down your system configuration used on the sheet).
Check item
Cause
Corrective action
(a) The GOT is restored by using the
reset switch on the GOT.
Restored
Not restored (Go to (b).)
It may be a temporary malfunction
due to noise.
Take the corrective action described in (4)-
(h).
(b) The GOT is restored by powering on
and off the GOT.
*1
Restored
Not restored (Go to (c).)
(c) The GOT is restored by resetting or
powering on and off the PLC CPU.
Restored
Not restored (Go to (d).)
(d) The GOT is restored by powering on
and off the GOT and the PLC CPU
simultaneously.
Restored
Not restored (Go to (e).)
(e) The GOT is restored by reconnecting
cables.
Restored
Not restored (Go to (f).)
The possible cause is a cable
connection fault.
Connect cables securely.
When the error occurs again, go to (5)
Actual product investigation.
(f) The GOT is restored by reinstalling
project data.
Restored
Not restored (Go to (g).)
In such a case where the GOT is
powered off during installation of
project data or OS, the data may be
corrupted.
Do not power off the GOT during data
transmission.
When the error occurs again, go to (5)
Actual product investigation.
(g) The GOT is restored by reinstalling
OS.
Restored
Not restored (Go to (h).)
(h) The GOT is restored by taking
corrective actions against noise described
in the corrective action column.
Restored
Not restored (Go to (i).)
It may be a temporary malfunction
due to noise.
Take corrective actions by following the
GOT installation status check sheet.
(i) The GOT is not restored even after the
corrective actions in (a) to (h) are taken.
-
Go to (5) Actual product investigation.
Summary of Contents for GOT SIMPLE GS2107-WTBD
Page 1: ...GRAPHIC OPERATION TERMINAL User s Manual GOT SIMPLE Series ...
Page 2: ......
Page 22: ...1 4 1 1 Features ...
Page 26: ...2 4 2 2 Component List ...
Page 34: ...4 4 4 3 Bottom ...
Page 42: ...5 8 5 2 EMC Directive Requirements ...
Page 48: ...6 6 6 5 Installation Procedure ...
Page 56: ...7 8 7 2 Wiring Inside and Outside the Panel ...
Page 68: ...9 10 9 3 Utility Display ...
Page 100: ...11 30 11 7 Keyword ...
Page 116: ...12 16 12 4 GOT internal device monitor ...
Page 134: ...13 18 13 3 Login Logout ...
Page 146: ...14 12 14 1 Time Setting and Display ...
Page 260: ...17 6 17 3 Clean ...
Page 266: ...20 2 ...
Page 282: ...23 2 ...
Page 288: ...REVISIONS 2 ...
Page 291: ......