16.3 FX3U-ENET-ADP Communication Setting Function
16 - 45
GOT S
ELF C
HECK (DE
BUG)
16
Step 5.
When the screen shown on the left
appears, the changed communication
set value of the FX3U-ENET-ADP is
written normally to the CPU. For
making valid the contents of setting,
turn OFF the power of the CPU, and
then turn it ON again. Change the
setting of the subnet mask pattern and
default router IP address using the
same procedure if necessary. An error
message appears in the following
cases. Touch the
key to return to
the step 1., and perform the setting
procedure again.
• When the CPU is running
The following error message
appears. Stop the running status of
the CPU.
• When a communication error occurs
Set the communication between the
GOT and the CPU to the normal
status.
• When the memory cassette is write-
protected
Set to OFF the write-protect switch
of the memory cassette.
• When writing to the CPU is
protected by the keyword
Clear the protection by the keyword
against writing.
Summary of Contents for GOT SIMPLE GS2107-WTBD
Page 1: ...GRAPHIC OPERATION TERMINAL User s Manual GOT SIMPLE Series ...
Page 2: ......
Page 22: ...1 4 1 1 Features ...
Page 26: ...2 4 2 2 Component List ...
Page 34: ...4 4 4 3 Bottom ...
Page 42: ...5 8 5 2 EMC Directive Requirements ...
Page 48: ...6 6 6 5 Installation Procedure ...
Page 56: ...7 8 7 2 Wiring Inside and Outside the Panel ...
Page 68: ...9 10 9 3 Utility Display ...
Page 100: ...11 30 11 7 Keyword ...
Page 116: ...12 16 12 4 GOT internal device monitor ...
Page 134: ...13 18 13 3 Login Logout ...
Page 146: ...14 12 14 1 Time Setting and Display ...
Page 260: ...17 6 17 3 Clean ...
Page 266: ...20 2 ...
Page 282: ...23 2 ...
Page 288: ...REVISIONS 2 ...
Page 291: ......