Simple mode parameter list
Sim
p
le
m
ode p
a
ra
met
e
r li
st
4
ADJ
US
TME
N
T
Parameter
Number
Name
Incre
ments
Initial
Value
Range
Applications
Refer
to
0
Torque boost
0.1%
6/4/3/2/
1.5/1%
*1
0 to 30%
Set to increase a starting torque or when the
motor with a load will not rotate, resulting in
an alarm [OL] and a trip [OC1]
*1
Initial values differ according to the inverter
capacity.
52
1
Maximum
frequency
0.01Hz
120/
60Hz
*2
0 to 120Hz
Set when the maximum and minimum
output frequency need to be limited.
*2
Initial values differ according to the inverter
capacity. (200V class and FR-F740-01160 or
less/ FR-F740-01800 or more)
53
2
Minimum
frequency
0.01Hz
0Hz
0 to 120Hz
3
Base frequency
0.01Hz
60Hz
0 to 400Hz
Set when the rated motor frequency is 50Hz.
Check the motor rating plate.
33
4
Multi-speed setting
(high speed)
0.01Hz
60Hz
0 to 400Hz
Set when changing the preset speed in the
parameter with a terminal.
44
5
Multi-speed setting
(middle speed)
0.01Hz
30Hz
0 to 400Hz
6
Multi-speed setting
(low speed)
0.01Hz
10Hz
0 to 400Hz
7
Acceleration time
0.1s
5/15s
*3
0 to 3600s
Acceleration/deceleration time can be set.
*3
Initial values differ according to the inverter
capacity. (FR-F720-00340 or less/FR-F720-
00490 or more, FR-F740-00170 or less/FR-
F740-00250 or more)
54
8
Deceleration time
0.1s
10/30s
*3
0 to 3600s
9
Electronic thermal
O/L relay
0.01/
0.1A
*4
Rated
inverter
output
current
0 to 500/
0 to 3600A
*4
Protect the motor from overheat by the
inverter.
Set the rated motor current.
*4
Setting increments and setting range differ
according to the inverter capacity.
(200V class and FR-F740-01160 or less/ FR-
F740-01800 or more)
32
60
Energy saving
control selection
1
0
0, 4, 9
The inverter output voltage is minimized
when using for fan and pump applications.
55
79
Operation mode
selection
1
0
0, 1, 2, 3, 4, 6, 7
Select the operation command location and
frequency command location.
57
125
Terminal 2
frequency setting
gain frequency
0.01Hz
60Hz
0 to 400Hz
Frequency for the maximum value of the
potentiometer (at 5V) can be changed.
47
126
Terminal 4
frequency setting
gain frequency
0.01Hz
60Hz
0 to 400Hz
Frequency at 20mA input can be changed.
49
160
User group read
selection
1
0
0, 1, 9999
Make extended parameters invalid
102
Inverter capacity
Initial
value
200V class
400V class
00046
00023
6%
00077 to 00167
00038 to 00083
4%
00250, 00340
00126, 00170
3%
00490 to 01540
00250 to 00770
2%
01870 or more
00930, 01160
1.5%
-
01800 or more
1%