18
Wiring
*1
Low indicates that the open collector output transistor is on (conducts).
High indicates that the transistor is off (does not conduct).
*2
Not output during inverter reset.
(3) Communication
(4) Control circuit terminal layout
(5) Wiring instructions
2)
Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main
and power circuits (including the 200V relay sequence circuit).
3)
Use two or more parallel micro-signal contacts or twin
contacts to prevent a contact faults when using contact inputs
since the control circuit input signals are micro-currents.
4)
Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
5)
Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp, etc.
6)
It is recommended to use the cables of 0.75mm
2
gauge for connection to the control circuit terminals.
If the cable gauge used is 1.25mm
2
or more, the front cover may be lifted when there are many cables running
or the cables are run improperly, resulting in an operation panel contact fault.
7)
The wiring length should be 30m (98.43feet) maximum.
A
n
al
og
CA
Analog current
output
Select one e.g. output frequency
from monitor items.
*2
The output signal is proportional to
the magnitude of the corresponding
monitoring item.
Output item:
Output frequency
(initial setting)
Load impedance
200
Ω
to 450
Ω
Output signal 0 to
20mADC
Instruction
Manual
(applied)
AM
Analog voltage
output
Output signal 0
to 10VDC
Permissible load
current 1mA
(load impedance
10k
Ω
or more)
Resolution 8 bit
Instruction
Manual
(applied).
Ty
p
e
Terminal
Symbol
Terminal
Name
Description
Rated
Specifications
Refer to
RS
-4
8
5
PU
connector
PU
connector
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard
: EIA-485(RS-485)
. Transmission format
: Multidrop
. Communication speed : 4800 to 38400bps
. Overall length
: 500m (1640.42feet)
23
RS-4
8
5
te
rm
in
a
ls
TXD+
Inverter
transmission
terminal
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard
: EIA-485(RS-485)
Transmission format
: Multidrop link
Communication speed : 300 to 38400bps
Overall length
: 500m (1640.42feet)
24
TXD-
RXD+
Inverter
reception
terminal
RXD-
SG
Ground
Terminal screw size: M3.5
Tightening torque: 1.2N·m
1)
Terminals 5, PC and SE are common to the I/O signals and isolated from each other. Do not ground.
Ty
p
e
Terminal
Symbol
Terminal
Name
Description
Rated
Specifications
Refer to
A1
B1
C1
A2
B2
C2 10E
10
2
5
4
1
AM
SD
RES
MRS
STOP
AU
RT
RH
RM
RL
PC
CS
JOG
STR
STF
SD
SD
FU
OL
IPF
SU
RUN
SE
CA
Micro signal contacts
Twin contacts