3.4 When the rated motor frequency is 50Hz (Pr.3)
First, check the motor rating plate. If a frequency given on the rating plate is "50Hz" only, always set
Pr. 3 Base
frequency
to "50Hz". Leaving the base frequency unchanged from "60Hz" may make the voltag low and the torque
insufficient. It may result in an inverter trip (E.OC
) due to overload.
Parameter
Number
Name
Initial Value
Setting Range
Description
3
Base frequency
60Hz
0 to 400Hz
Set the frequency when the motor
rated torque is generated.
Changing example
Change
Pr. 3 Base frequency
to 50Hz according to the motor rated frequency.
REMARKS
When an alarm trip (E.OC
) occurs, release the start command, and decrease the Pr. 1 value 1% by 1% to reset.
Refer to
page 74
for reset.
3.
Press to choose the parameter
setting mode.
Flicker
···
Parameter setting complete!!
7.
Press to set.
·
By turning , you can read another parameter.
·
Press to show the setting again.
·
Press twice to show the next parameter.
4.
Turn until
Pr. 3 Base frequency
appears.
1.
Screen at powering on
The monitor display appears.
2.
Press to choose the PU operation
mode.
PU indication is lit.
Display
Operation
The parameter
number
read previously
appears.
5.
Press to show the currently set
value. (60Hz)
6.
Turn counterclockwise to
change the set value to "50.0". (50Hz)