338
Communication
operation command
source
1
0
0
Operation command source
communication
1
Operation command source external
339
Communication
speed command
source
1
0
0
Speed command source communication
1
Speed command source external
(Frequency setting from communication is
invalid, terminal 2 and 1 setting from
external is valid)
2
Speed command source external
(Frequency setting from communication is
valid, terminal 2 and 1 setting from
external is invalid)
550
NET mode
operation command
source selection
1
9999
0
Communication option valid
1
Inverter RS-485 terminal valid
9999
Automatic recognition of the
communication option
Normally, the RS-485 terminals are valid.
Communication option is valid when the
communication option is mounted.
551
PU mode operation
command source
selection
1
2
1
Select the RS-485 terminals as the PU
operation mode control source.
2
Select the PU connector as the PU
operation mode control source.
—
340
Refer to
Pr.79
.
341 to 343
Refer to
Pr.117 to Pr.124
.
Rem
o
te
out
put
fu
nct
ion
(R
EM
signal)
495
Remote output
selection
1
0
0
Remote output data clear at powering off
1
Remote output data retention even at
powering off
496
Remote output data 1
1
0
0 to 4095
Output terminal can be switched on and off.
×
×
×
497
Remote output data 2
1
0
0 to 4095
×
×
×
T
o
d
e
te
rm
in
e
th
e maint
e
nance
tim
e
o
f p
a
rt
s
.
503
Maintenance timer
1
0
0 (1 to 9998)
Display the cumulative energization time
of the inverter in 100h increments.
Reading only
Writing the setting of "0" clears the
cumulative energization time.
×
×
×
504
Maintenance timer
alarm output set time
1
9999
0 to 9998
Set the time taken until when the maintenance
timer alarm output signal (Y95) is output.
×
9999
No function
—
549
Refer to
Pr.117 to Pr.124
.
550, 551
Refer to
Pr.338 and Pr.339
.
Current
a
v
erage
value
m
oni
to
r signal
555
Current average
time
0.1s
1s
0.1 to 1.0s
Set the time taken to average the current
during start bit output (1s).
556
Data output mask
time
0.1s
0s
0.0 to 20.0s
Set the time for not obtaining (mask)
transient state data.
557
Current average
value monitor signal
output reference
current
0.01/
0.1A
*15
Rated
inverter
current
0 to 500/
0 to 3600A
*15
Set the reference (100%) for outputting
the signal of the current average value.
*15 Setting increments and setting range
differ according to the inverter capacity.
(200V class and FR-F740-01160 or
less/FR-F740-01800 or more)
—
563, 564
Refer to
Pr.52
.
Mu
lt
ip
le
r
a
ti
n
g
se
le
ct
io
n
570
Multiple rating
setting
1
0
0
SLD: Ambient temperature 40°C,
overload 110% 60s, 120% 3s
×
×
1
LD: Ambient temperature 50°C, overload
120% 60s, 150% 3s
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled
Summary of Contents for FR-F700 Series
Page 134: ...MEMO ...