3
Peripheral devices
2
INS
T
ALLA
TIO
N
A
ND
WIRING
2.1 Peripheral devices
Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to the
capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
400V class
Motor
Output
(kW(HP))
*1
Applicable Inverter Type
Breaker Selection
*2
Input Side Magnetic
Contactor
*3
Reactor connection
with commercial
power-supply
operation
Reactor connection
without
with
without
with
0.75 (1)
FR-F720-00046-NA
30AF 10A
30AF 10A
30AF 10A
S-N10
S-N10
1.5 (2)
FR-F720-00077-NA
30AF 15A
30AF 15A
30AF 15A
S-N10
S-N10
2.2 (3)
FR-F720-00105-NA
30AF 20A
30AF 15A
30AF 20A
S-N10
S-N10
3.7 (5)
FR-F720-00167-NA
30AF 30A
30AF 30A
30AF 30A
S-N20, N21
S-N10
5.5 (7.5)
FR-F720-00250-NA
50AF 50A
50AF 40A
50AF 50A
S-N25
S-N20, N21
7.5 (10)
FR-F720-00340-NA
100AF 60A
50AF 50A
100AF 60A
S-N25
S-N25
11 (15)
FR-F720-00490-NA
100AF 75A
100AF 75A
100AF 75A
S-N35
S-N35
15 (20)
FR-F720-00630-NA
225AF 125A
100AF 100A
225AF 125A
S-N50
S-N50
18.5 (25)
FR-F720-00770-NA
225AF 150A
225AF 125A
225AF 150A
S-N65
S-N50
22 (30)
FR-F720-00930-NA
225AF 175A
225AF 150A
225AF 175A
S-N80
S-N65
30 (40)
FR-F720-01250-NA
225AF 225A
225AF 175A
225AF 225A
S-N95
S-N80
37 (50)
FR-F720-01540-NA
400AF 250A
225AF 225A
400AF 250A
S-N150
S-N125
45 (60)
FR-F720-01870-NA
400AF 300A
400AF 300A
400AF 350A
S-N180
S-N150
55 (75)
FR-F720-02330-NA
400AF 400A
400AF 350A
600AF 500A
S-N220
S-N180
Motor
Output
(kW(HP))
*1
Applicable Inverter Type
Breaker Selection
*2
Input Side Magnetic
Contactor
*3
Reactor connection
with commercial
power-supply
operation
Reactor connection
without
with
without
with
0.75 (1)
FR-F740-00023-NA
30AF 5A
30AF 5A
30AF 5A
S-N10
S-N10
1.5 (2)
FR-F740-00038-NA
30AF 10A
30AF 10A
30AF 10A
S-N10
S-N10
2.2 (3)
FR-F740-00052-NA
30AF 10A
30AF 10A
30AF 15A
S-N10
S-N10
3.7 (5)
FR-F740-00083-NA
30AF 20A
30AF 15A
30AF 20A
S-N10
S-N10
5.5 (7.5)
FR-F740-00126-NA
30AF 30A
30AF 20A
30AF 30A
S-N20
S-N11, N12
7.5 (10)
FR-F740-00170-NA
30AF 30A
30AF 30A
30AF 30A
S-N20
S-N20
11 (15)
FR-F740-00250-NA
50AF 50A
50AF 40A
50AF 50A
S-N20
S-N20
15 (20)
FR-F740-00310-NA
100AF 60A
50AF 50A
100AF 60A
S-N25
S-N20
18.5 (25)
FR-F740-00380-NA
100AF 75A
100AF 60A
100AF 75A
S-N25
S-N25
22 (30)
FR-F740-00470-NA
100AF 100A
100AF 75A
100AF 100A
S-N35
S-N25
30 (40)
FR-F740-00620-NA
225AF 125A
225AF 100A
225AF 125A
S-N50
S-N50
37 (50)
FR-F740-00770-NA
225AF 150A
225AF 125A
225AF 150A
S-N65
S-N50
45 (60)
FR-F740-00930-NA
225AF 175A
225AF 150A
225AF 175A
S-N80
S-N65
55 (75)
FR-F740-01160-NA
225AF 200A
225AF 175A
225AF 200A
S-N80
S-N80
75 (100)
FR-F740-01800-NA
225AF 225A
225AF 225A
S-N95
90 (125)
FR-F740-01800-NA
225AF 225A
400AF 300A
S-N150
110 (150)
FR-F740-02160-NA
225AF 225A
400AF 350A
S-N180
132 (200)
FR-F740-02600-NA
400AF 400A
400AF 400A
S-N220
160 (250)
FR-F740-03250-NA
400AF 400A
600AF 500A
S-N300
185 (300)
FR-F740-03610-NA
400AF 400A
600AF 500A
S-N300
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200/400VAC 50Hz.
*2
Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to page 127.)
*3
The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is used for emergency stop during motor
driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the
MC with class AC-3 rated current for the motor rated current.
*4
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc.
Identify the cause of the trip, then remove the cause and power on the breaker.
MCCB
INV
MCCB
INV
IM
IM