Wiring
2.4 Wiring
2.4.1
Terminal connection diagram
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm (3.94inches) away from the power cables.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
Three-phase AC
power supply
MCCB
Jumper
R/L1
S/L2
T/L3
R1/L11
S1/L21
PC
10E
(+10V)
10
(+5V)
2
3
1
1
4
Control input signals (No voltage input allowed)
Jumper
Motor
Relay output 1
(Alarm output)
C1
B1
A1
U
V
W
AM
5
*1
Main circuit terminal
Control circuit terminal
MC
Main circuit
Control circuit
C2
B2
A2
Relay output 2
Relay output
IM
AU
PTC
TXD+
TXD-
RXD+
RXD-
SG
SINK
SOURCE
Terminal functions
vary with the output
terminal assignment
(
Pr. 195, Pr. 196)
Terminal functions
vary with the output
terminal assignment
(
Pr. 190 to Pr. 194)
Terminal functions
vary with the input
terminal assignment
(
Pr. 178 to Pr. 189
)
*3
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
RES
AU
CS
SD
RUN
SU
IPF
OL
FU
SE
Connector for
with/without
EMC filter
ON
OFF
VCC
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k
Ω
Auxiliary input
(+)
(-)
2
(Analog common)
0 to 5VDC
0 to 10VDC
selected
4 to 20mADC
*4
5
PU
connector
Terminal 4 input
(Current input)
Terminating
resistor
Connector
for plug-in option
connection
*5. It is recommended to use
2W1k
Ω
when the
frequency setting signal is
changed frequently.
(+)
(-)
0 to 5VDC
0 to 10VDC
selected *4
GND
RS-485 terminals
Data transmission
Data reception
4 to 20mADC
*4
selected
0 to
±5VDC
0 to
±10VDC
(-)
(+)
(0 to 10VDC)
Analog signal output
Frequency detection
Open collector output common
Sink
/source common
Running
Up to frequency
Instantaneous
power failure
Overload
Open collector output
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Output stop
Reset
*3. AU terminal
can be used
as PTC input
terminal.
Middle speed
High speed
Low speed
Jog mode
Second function selection
Multi-speed
selection
Forward
rotation
start
Reverse
rotation
start
Start self-holding selection
PR
*7
PX
*7
Jumper
*7.
*5
*4. Terminal input
specifications can be
changed by analog input
specifications switchover
(
Pr. 73, Pr. 267
).
(Permissible load
current 100mA)
5V
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
*2
Please do not remove or use
terminals PR and PX or the
jumper connected.
N/-
P/+
Option connector 1
P1
Brake resistor
(Option)
Brake unit
(Option)
CN8
*6
Sink logic
Ground
Ground
Ground
(0 to 20mADC)
(-)
(+)
CA
(0 to 20mADC)
(-)
(+)
CA
(0 to 20mADC)
Analog current output
(-)
(+)
CA
24VDC power supply
(Common for external power supply transistor)
Contact input common
*6. The CN8 connector is
provided for
the FR-F740-01800 or more.
*1.
DC reactor (FR-HEL)
The DC reactor supplied with the
FR-F740-01800 or more should be
connected to these terminals. When
a DC reactor is connected, remove the
jumper across P1-P/+ for the 200V class
and FR-F740-01160 or less.
*8. The FR-F720-00046 and 00077
are not provided with the ON/OFF
connector of the EMC filter.
*8