121
Extended parametersExtended parameters
Extended p
a
ramete
r
li
s
t
—
571
Refer to
Pr.13
.
573
Refer to
Pr.73
.
575 to 577
Refer to
Pr.127 to Pr.134
.
Pum
p
f
u
nct
ion
578
Auxiliary motor
operation selection
1
0
0
No auxiliary motor operation
1 to 3
Set the number of auxiliary motors to
be run
579
Motor connection
function selection
1
0
0
Basic system
1
Alternative system
2
Direct system
3
Alternative-direct system
580
MC switching
interlock time
0.1s
1s
0 to 100s
You can set the MC switching interlock
time when
Pr. 579
=2.
581
Start waiting time
0.1s
1s
0 to 100s
You can set the time from MC switch-
over to a start when
Pr. 579
=2. Set this
time a little longer than the MC
switching time.
582
Auxiliary motor
connection-time
deceleration time
0.1s
1s
0 to 3600s
You can set the deceleration time for
decreasing the output frequency of the
inverter if a motor connection occurs
under advanced PID control.
9999
The output frequency is not forcibly
changed.
583
Auxiliary motor
disconnection-time
acceleration time
0.1s
1s
0 to 3600s
You can set the acceleration time for
increasing the output frequency of the
inverter if a motor disconnection occurs
under advanced PID control.
9999
The output frequency is not forcibly
changed.
584
Auxiliary motor 1
starting frequency
0.01Hz
60Hz
0 to 400Hz
Set the frequency to connect an
auxiliary motor.
585
Auxiliary motor 2
starting frequency
0.01Hz
60Hz
0 to 400Hz
586
Auxiliary motor 3
starting frequency
0.01Hz
60Hz
0 to 400Hz
587
Auxiliary motor 1
stopping frequency
0.01Hz
0Hz
0 to 400Hz
Set the frequency to open an auxiliary
motor.
588
Auxiliary motor 2
stopping frequency
0.01Hz
0Hz
0 to 400Hz
589
Auxiliary motor 3
stopping frequency
0.01Hz
0Hz
0 to 400Hz
590
Auxiliary motor start
detection time
0.1s
5s
0 to 3600s
You can set the delay time until the
auxiliary motor is started.
591
Auxiliary motor stop
detection time
0.1s
5s
0 to 3600s
You can set the delay time until the
auxiliary motor is stopped.
—
611
Refer to
Pr.57
and Pr.58
.
867, 869
Refer to
Pr.54 to Pr.56
.
872
Refer to
Pr.251
.
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled