44
Operation by the start command of the
terminal block (external operation)
3.6.2
Use switches to give a start command and a frequency command
(multi-speed setting) (Pr. 4 to Pr.6)
[Connection diagram]
POINT
· Start command by terminal STF (STR)-SD
· Frequency command by terminal RH, RM, RL and STR-SD
· [EXT] must be lit. (When [PU] is lit, switch it to [EXT] with
.)
· The initial values of the terminals RH, RM, RL are 60Hz, 30Hz, and 10Hz. (Use
Pr. 4
,
Pr. 5
and Pr. 6
to change.)
· Operation at 15-speed can be performed by turning two (or three) terminals simultaneously.
(Refer to the
Instruction Manual (applied).)
Changing example
Set "50Hz" in
Pr. 4 Multi-speed setting (high speed)
and turn on terminal RH and STF (STR)-
SD to operate.
Three-phase
AC power supply
Motor
Inverter
R/L1
S/L2
T/L3
U
V
W
High speed
Middle speed
Low speed
RH
RM
RL
Forward
rotation start
Reverse
rotation start
STF
STR
SD
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Speed 4
Speed 5
Speed 6
Speed 7
Time
RH
RM
RL
The parameter number
read previously appears.
ON
Display
Operation
1.
Power on
→
operation mode check
For the initial setting, the inverter operates in
the external operation mode [EXT] when
powering on. Check that the operation
command indication is [EXT].
If not displayed, press to change to the
external [EXT] operation mode. If the operation
mode still does not change, set
Pr. 79
to change to
the external operation mode.
2.
Press to choose the parameter
setting mode.
3.
Turn until (
Pr. 4
) appears.
6.
Press to set.
Flicker ··· Parameter setting complete!!
5.
Turn counterclockwise to change it to
the setting value of " ". (50.00Hz)
4.
Press to read the currently set value.
" "(initial value) appears. (60.00Hz)
(Refer to page 57.)