110
Extended parametersExtended parameters
Extended p
a
ramete
r
li
s
t
O
perat
io
n m
ode
se
le
c
tion
79
Operation mode
selection
1
0
0
External/PU switchover mode
1
Fixed to PU operation mode
2
Fixed to External operation mode
3
External/PU combined operation mode 1
4
External/PU combined operation mode 2
6
Switchover mode
7
External operation mode (PU operation
interlock)
340
Communication
startup mode
selection
1
0
0
As set in
Pr.79
.
1, 2
Started in the network operation mode.
When the setting is "2", it will resume the pre-
instantaneous power failure operation mode
after an instantaneous power failure occurs.
10, 12
Started in the network operation mode.
Operation mode can be changed between
the PU operation mode and network
operation mode from the operation panel.
When the setting is "12", it will resume the pre-
instantaneous power failure operation mode
after an instantaneous power failure occurs.
Simple magn
et
ic
fl
ux
v
e
ct
or
cont
rol
80
Motor capacity
(simple magnetic
flux vector control)
0.01kW/
0.1kW
*13
9999
0.4 to 55/
0 to 3600kW
*13
To select the simple magnetic flux vector
control, set the capacity of the motor
used.
*13 The setting depends on the inverter
capacity (200V class and FR-F740-
01160 or less/FR-F740-01800 or more)
9999
V/F control is performed
90
Motor constant (R1)
0.001
Ω
/
0.01m
Ω
*
9999
0 to 50
Ω/
0 to 400m
Ω
*14
Used to set the motor primary resistance
value.
(Normally setting is not necessary.)
*14 The setting depends on the inverter
capacity (200V class and FR-F740-
01160 or less/FR-F740-01800 or more)
×
9999
Use the Mitsubishi motor (SF-JR, SF-
HRCA) constants
Ad
ju
s
table 5
point
s V/
F
100
V/F1
(first frequency)
0.01Hz
9999
0 to 400Hz,
9999
Set each points (frequency, voltage) of V/
F pattern.
9999: No V/F setting
101
V/F1 (first
frequency voltage)
0.1V
0V
0 to 1000V
102
V/F2
(second frequency)
0.01Hz
9999
0 to 400Hz,
9999
103
V/F2 (second
frequency voltage)
0.1V
0V
0 to 1000V
104
V/F3
(third frequency)
0.01Hz
9999
0 to 400Hz,
9999
105
V/F3 (third
frequency voltage)
0.1V
0V
0 to 1000V
106
V/F4
(fourth frequency)
0.01Hz
9999
0 to 400Hz,
9999
107
V/F4 (fourth
frequency voltage)
0.1V
0V
0 to 1000V
108
V/F5
(fifth frequency)
0.01Hz
9999
0 to 400Hz,
9999
109
V/F5 (fifth
frequency voltage)
0.1V
0V
0 to 1000V
71
Refer to
page
108.
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled
Summary of Contents for FR-F700 Series
Page 134: ...MEMO ...